Seite - 47 -
04.10.2008 / LSV - JWh/ Rev. 02
DIGIDOS 24 AT
© 2008
OPERATION
Operation
3.3 Operation
3.3.1 Requirements for Foam Operation
- Commissioning the water pump
IMPORTANT!
The operating instructions of the pump manufacturer
absolutely must be heeded.
- Press „FOAM“ on the display.
- Check whether there is a sufficient supply of foam compound
in the foam compound tank (display).
- Use function key F1 to select the „Direct-injection foam
proportioner“.
- Use function keys F2 „+%“ and F3 „-%“ to select the
proportioning rate.
- Use function key F4 to select from where the foam compound
is to be drafted: „TANK A“, „TANK B“ or „EXTERNAL
DRAFTING“.
- Use the Enter key „
“ to confirm the selection
- Open pressure outlets
- Set the pump pressure (pump operation) to the desired
value.
Foam
Direct-injection foam
proportioner
Enter