TROUBLESHOOTING
5 MALFUNCTIONS AND THEIR ELIMINATION
Drive malfunctions: see the operating instructions of the manufacturer
Pump malfunctions: see the operating instructions of the manufacturer
Malfunctions in CAFS and
foam compound operation: see the measures described in chapter 4
Malfunctions that can not be shown on the display.
MALFUNCTIONS CAUSE REMEDY
Foam pump is - Water flow - Check water flow meter
activated, but sensor defective
no foam is - Air in the foam pump - Ventilate the foam pump (foam
conveyed pump is flooded)
- Foam flow meter - Service technician
defective
Poor foam - Foam flow meter - Service technician
quality defective
IMPORTANT!
If you are unable to identify or remedy malfunctions yourself, please contact Rosenbauer
customer service at the Leonding works, or your nearest Rosenbauer service point.