Maintenance
ATTENTION !
To keep the fire fighting superstructure in functioning condition
below 0
°
Celsius please take appropriate measures (e.g. engage
the water tank heating, park vehicle in non-freezing garage,...).
Drainage of the Pump System / Operation in Cold Climates
- Remove blind coupling of pressure outlet (J11) or disconnect
the pressure hose.
◊
Open the right discharge valve (J10).
- Drying the priming pump:
◊
Shift pump system to manual mode - please refer to the
"Manual Pump Operation" chapter - this is to prohibit
automatic opening of the water tank suction valve.
◊
Engage the pump - please refer to the "Engaging the Pump"
chapter.
◊
Press switch (S3) for approx. 5 seconds time.
◊
Disengage the pump.
- Drainage of the right hose reel:
◊
Please refer to the "Rapid Intervention System" chapter.
- Drainage of the electric foam compound pump:
◊
Please refer to the "Flushing of the electric foam compound
pump" chapter.
- Drainage of right tank fill line:
◊
Remove blind couplings of tank fill connections (J30).
◊
Open tank fill valves (J29).
- Drain the deluge filter by closing shut off valve (J74) and
opening drain valve (J76).
- Operate all ball valves several times; keep ball valves in half
open position to allow drainage of the valve casing.
- Wait until the pump system is drained.
- Close all pressure outlets and drain valves, secure with blind
couplings.
◊
Press all switches again, with the integrated pilot lamp
illuminates.