Hardware Installation and Reference Guide Appendixes
28
The cable management brackets and cabling troughs inside and outside the cabinet should
be smooth without sharp corners.
The metal hole traversed by cables should have a smooth and fully rounding surface or an
insulated lining.
Use cable ties to bundle up cables properly. Please do not connect two or more cable ties to
bundle up cables.
After bundling up cables with cable ties, cut off the remaining part. The cut should be
smooth and trim, without sharp corners.
Figure 7-4 Bundling up Cables (2)
When cables need to be bent, you should first bundle them up. However, the buckle cannot
be bundled within the bend area. Otherwise, considerable stress may be generated in
cables, breaking cable cores.
Figure 7-5 Bundling up Cables (3)
Cables not to be assembled or remaining parts of cables should be folded and placed in a
proper position of the rack or cable trough. The proper position refers to a position that does
not affect device running or damage the device or cable.
220 V and 48 V power cords must not be bundled on the guide rails of moving parts.
The power cords connecting moving parts such as grounding cables should be reserved
with some access after being assembled to avoid suffering tension or stress. After the