10.2. Exchanger” – {R_0_10, R_On/Off, B_0_10, B_DMP}, factory setting depends on the type of the
unit
R_0_10 – 0–10V control of the rotor heat exchanger
R_On/Off – On/Off control of the rotor heat exchanger using the relay
B_0_10 – 0–10 V control of the bypass valve of the plate hater exchanger
B_DMP – Control of the three-position bypass valve of the plate heat exchanger
10.3. Vent. Unit” – {TK, RHEC, RHC}, factory setting depends on the type of the unit
TK – Supply chamber, section 10.2 is not applicable
RHEC – Recuperator with the heat exchanger control
RHC – Recuperator without the heat exchanger control
10.4. Fans Type” – {EC, AC}, factory setting depends on the type of the unit
EC – control of the EC motors using 0–10 V signal
AC – control of the AC motors using three fi xed voltages
11. PSI.” – when pressure support is selected, min. and max. limits are set for the pressure converter
11.1. min_0V” – {0ppm–2000} % Pa, factory setting 0
11.2. max_10V” – {0ppm–2000} %, Pa, factory setting 300
12. CO2” – when CO2 control is selected, min. and max. limits are set for the CO2 converter
12.1. min_0V” – {0ppm–2000} %, ppm, factory setting 0
12.2. max_10V” – {0ppm–2000} %, ppm, factory setting 1000
13. Vent. Control” – setting of the indications for fans
13.1. SAF” – {Percent, Pressure} settings for the indications of the supply air motor %, Pa, factory set-
ting (Percent)
13.2. EAF” – {Percent, Pressure, SAF+Pressure} settings for the indications of the extracted air motor
%, Pa, factory setting (Percent)
13.3. SAF+Pressure” – extracted air motor change differs from the supply only by the set value
13.4. CO2” – {On/Off} extracted air CO2 sensor, factory setting (Off)
13.5. ResetToFactorySettings” – after switching “OK”, factory settings are saved. CAUTION! The unit
and panel reloads
14. Misc” – stop conditions for the unit depends on the connection of the panel
14.1. RC NC” – {On, Off}, factory setting (Off)
On – (Remote Control) No control panel, the unit is stopped
Off – (Remote Control) No control panel, the unit is on
This setting is not applicable if the unit is controlled via ModBus interface