7-12 EB 8331-4 EN
Start-up and conguration
Table 7-1: Modbus RTU parameter
(setting in the communication level, see the 'Operation' section)
Code Parameters Display/select (select ESC to cancel)
Serial interface
A51 Communication ENAB(enabled)
DISA (disabled)
Interface module
A61 Communication ENAB(enabled)
DISA (disabled)
A62 Interface module 485 (RS-485)
USB(USB)
ETH(Ethernet)
NONE (none)
A63 Protocol AUTO (automatic: SSP, Modbus)
MODX (Modbus, adjustable)
Modbus interface module
A64 Station address 1 to 247
A65 Baudrate(inBaud) 1200
2400
4800
9600
192 (19200)
A66 Stop bits and parity 1SNP (1 stop bit, no parity)
1SEP (1 stop bit, even parity)
1SOP (1 stop bit, odd parity)
2SNP (2 stop bits, no parity)
A67 Busfailuremonitoringinmin(timeout) 0 to 99
A00 Exit level > ESC