7.12 Faults
On the occurrence of a fault, the fault
indication icon appears at the bottom of
the display.
If the fault indication icon appears after a
parameter code setting has been changed,
this indicates that these settings do not
match the values determined during initial-
ization. See Code E1 (refer to section 8).
Press or past Code
P 0
or
P 20,
the
respective error code
E0
to
E15
together
with
ERR
appear on the display.
Refer to the code list in section 8 for the
cause of the errors and the recommended
action.
Example:
If, for instance, a travel has been entered
over Code
P4
(nominal range) which is
larger than the maximum valve travel possi-
ble, the initialization process would be inter-
rupted (error code
E2
) because the rated
travel would not have been reached (error
code
E6
). The valve moves to the fail-safe
position (
S
indicated on the display).
Display of the fault
indication
The nominal range (Code
P4
) must be
changed and the positioner re-initialized to
remedy this problem.
Reset error codes
The error codes
E0
and
E8
can be reset as
follows:
Press or until the error code appears.
Press ,
ESC
appears.
Press or ,
RST
appears.
Press to reset error.
The resetting procedure can be canceled by
pressing when
ESC
appears.
42 EB 8394 EN
Start-up – Settings