Appendix
11.3 Code list
− Values in square brackets [ ] are default settings.
− Codes marked by an asterisk (*) indicate that the positioner needs to be re-initialized after-
wards
Code Reading/values Description
P0 Status reading with
basic information
Thereadingindicatesthevalvepositionorangleofrotationin%
when the positioner is initialized.
Press
to show the position of the lever in relation to the mid-
axis.
P1 Reading direction Thereadingdirectionofthedisplayisturnedby180°.
P2* ATO/ATC
[ATO]
Parameter to adapt the positioner to how the control valve func-
tions:
ATO: Air to open (valve CLOSED in fail-safe position)
ATC: Air to close (valve OPEN in fail-safe position)
P3* Pin position
17/25/[35]/50/
70/100/200/90°
The follower pin must be inserted in the proper position depending
onthevalvetravel/openingangle(seepage21).
P4* Nominal range
[MAX]
Thepossibleadjustmentrangecanbeselectedinstepsof0.5mm
depending on the selected pin position:
17 From 3.5 to 17.5mm , alternatively MAX
25 From 5.0 to 25.0mm , alternatively MAX
35 From 7.0 to 35.0mm , alternatively MAX
50 From 10.0 to 50.0mm, alternatively MAX
70 From 14.0 to 70.0mm, alternatively MAX
100 From 20.0 to 100.0mm, alternatively MAX
200 From 40.0 to 166.0mm, alternatively MAX
For 90° Maximum range only, if P3 = 90°
(MAX=Maximumpossibletravel)
Note