122 EB 8384-2 EN
Malfunctions
Example:
S
Example:
Error caused by pin po-
sition
Î Refertothecodelist(section11.4)for
possible causes and the recommended
action.
Fault alarm output
'Maintenance alarm' as the condensed state
causes the optional fault alarm output to be
switched.
The 'Function check' condensed state can
also activate the fault alarm output
(Code32).
The'Maintenancerequired/Maintenance
demanded' condensed state and 'Out of
specication'canalsoactivatethefault
alarmoutput(Code33).
9.1 Conrming error messages
Enable conguration:
1. Turn untilCode3appears(read-
ing: No).
2. Press , the code number 3 blinks.
3. Turn
until YES appears.
4. Press
toconrm(reading: ).
Conrming error message:
1. Turn until the the error code that
you want appears.
2. Press toconrmtheerrormessage.
9.2 Emergency action
Fail-safeactionistriggeredbythei/pcon-
verter or solenoid valve and upon supply air
failure. The positioner fully discharges its
pneumatic output to the atmosphere, causing
the mounted actuator to be vented. As a re-
sult, the valve moves to the fail-safe position.
The fail-safe position depends on how the
springs are arranged in the pneumatic actu-
ator (air-to-close or air-to-open).
Whenthesupplyairfails,whentheoptional
solenoid valve is triggered and after reach-
ing the shutdown signal, all positioner func-
tions,exceptopen/closedloopcontrol,re-
main active (including diagnostics as well as
position and status feedback).
Emergency action in the event of valve or ac-
tuator failure is described in the associated
valve and actuator documentation.
Î The plant operator is responsible for
emergency action to be taken in the
plant.
Tip