2.3 Measured data
TROVIS-VIEW 3: [Diagnosis > Emergency
Shut Down > Measured data]
The following parameters are measured dur
-
ing the partial stroke test:
4
Valve position x
4
Reference variable w
4
Setpoint deviation e
4
Drive signal y
4
Time
These parameters are saved in a FIFO mem
-
ory with a capacity of 100 measured values.
The last 100 measured values of the parame
-
ters determined during the partial stroke test
are listed in the [Measured data] folder.
2.4 Resetting ESD
TROVIS-VIEW 3: [Diagnosis > Emergency
Shut Down > Reset ESD]
Using the
Reset ESD
parameter, the param
-
eters of the ESD functions and the data log
-
ger are reset to their default values.
Any recorded measured values, error
messages, and data logger data are de
-
leted.
Note! After resetting the parameter, the
positioner is in the MAN operating mode.
The ESD mode needs to be reactivated.
EB 8388-1 EN 15
ESD functions