EB 8389 EN 115
Appendix
Code
No.
Parameter – Readings/
values [default setting]
Description
Codes with marked with an asterisk (*) must be enabled with Code3 prior to conguration.
49* h5 Operating point limit
55.0 to 100.0% of
reference variable,
[75.0%]
Types3730-2/-3 and Type3731-3 only
Valve is moved to the operating point when the operating point limit
is exceeded.
h6 Unassigned
h7 Limit value travel anal-
ysis
[0.6] to 30.0s
Types3730-2/-3 and Type3731-3 only
Time limit for difference between reference value and currently re-
corded value. Determines the difference at which a message is gen-
erated.
h8 Limit value time analy-
sis
0.1 to 100.0% of the
valve position, [0.3%]
Types3730-2/-3 and Type3731-3 only
Travel limit for difference between reference value and currently re-
corded value. Determines the difference at which a message is gen-
erated.
h9 Status classication for
on/off
C Maintenance required
OK No message
CR Maintenance demanded
b Maintenance alarm
S Out of specication
Read only
9.1.1 PROFIBUS parameter (Type3730-4)
Code
No.
Parameter – Readings/
values [default setting]
Description
Codes with marked with an asterisk (*) must be enabled with Code3 prior to conguration.
48* F0 Firmware rev.
Communication
F1 Binary input 1 0 Not active
1 Active
F2 Binary input 2 0 Not active
1 Active