126 EB 8384-3 EN
Appendix
11.3 Code list
Code
no.
Parameter–Readings/
values [default setting]
Description
Codes marked with an asterisk (*) must be enabled with Code3 prior to conguration.
0 Operating mode
[MAN]
Manual mode
AUtO Automatic mode
SAFE Fail-safe position
ESC Stop
Switchover from automatic to manual mode is bumpless.
In fail-safe position, the S icon is displayed.
In MAN and AUtO mode, the system deviation is represented by the
bar graph elements.
Thereadingindicatesthevalvepositionorangleofrotationin%
when the positioner is initialized. If the positioner is not initialized,
the position of the lever in relation to the longitudinal axis is dis-
played in degrees (°).
1 Manual w
[0]to100%ofthenomi-
nal range
Adjust the manual set point with the rotary pushbutton. The current
travel/angleisdisplayedin%whenthepositionerisinitialized.If
the positioner is not initialized, the position of the lever in relation to
the longitudinal axis is indicated in degrees (°).
ItcanonlybeselectedwhenCode0=MAN
2 Reading direction
1234,
1234
, ESC
The reading direction of the display is turned by 180°.
3 Enable conguration
[No], YES, ESC
Enables changing of data (automatically deactivated when the rota-
rypushbuttonhasnotbeenoperatedfor120s).HART blinks on the
display when the on-site operation is locked over HART
®
communi-
cation. Codes marked with an asterisk (*) can only be read and not
overwritten. Similarly, codes can only read over the SSP interface.