EB 8384-3 EN 127
Appendix
Code
no.
Parameter–Readings/
values [default setting]
Description
4* Pin position
[No], 17, 25, 35, 50, 70,
100,200,300mm,90°
with rotary actuators, ESC
If you select a pin position
in Code 4 that is too small,
the positioner switches to
SAFE mode for reasons of
safety.
Follower pin must be mounted in the proper position depending on
thevalvetravel/openingangle.
Pin position must be entered for nominal (NOM) or substitute (SUb)
initialization.
Pin position Standard Adjustment range
Code4 Code5 Code5
17 7.5 3.6 to 17.7
25 7.5 5.0 to 25.0
35 15.0 7.0 to 35.4
50 30.0 10.0 to 50.0
70 40.0 14.0 to 70.7
100 60.0 20.0 to 100.0
200 120.0 40.0 to 200.0
90° 90.0 24.0 to 100.0
5* Nominal range
mm or angle °, ESC
Nominal valve travel or opening angle must be entered for nominal
(NOM) or substitute (SUb) initialization.
The possible adjustment range depends on the pin position from the
tableforCode4.
Indicatesmaximumtravel/anglereachedduringinitializationafter
initialization has been successfully completed.
6* Init mode
[MAX] Maximum range
NOM Nominal range
MAN Manual setting
SUb Emergency mode
ZP Zero calibration
ESC Stop
Select the initialization mode
MAX: Travel/angleoftheclosurememberfromtheCLOSED
position to the opposite stop in the actuator.
NOM: Travel/angleoftheclosuremembermeasuredfromthe
CLOSED position to the indicated OPEN position.
MAN: Manually selected range
SUb: Substitute calibration (without initialization)
7* w/x
[ää] Increasing/increas-
ing
äæ
Increasing/decreas-
ing
ESC
Directionofactionofthesetpointwinrelationtothetravel/anglex
Automatic adaptation:
AIR TO
OPEN:
On completing initialization, the direction of action
remainsincreasing/increasing(ää). A globe valve opens
as the set point increases.
AIR TO
CLOSE:
On completing initialization, the direction of action
changestoincreasing/decreasing(äæ). A globe valve
closes as the set point increases.