EB 8384-3 EN 127
Appendix
Code
no.
Parameter–Readings/
values [default setting]
Description
4* Pin position
[No], 17, 25, 35, 50, 70,
100,200,300mm,90°
with rotary actuators, ESC
If you select a pin position
in Code 4 that is too small,
the positioner switches to
SAFE mode for reasons of
safety.
Follower pin must be mounted in the proper position depending on
thevalvetravel/openingangle.
Pin position must be entered for nominal (NOM) or substitute (SUb)
initialization.
Pin position Standard Adjustment range
Code4 Code5 Code5
17 7.5 3.6 to 17.7
25 7.5 5.0 to 25.0
35 15.0 7.0 to 35.4
50 30.0 10.0 to 50.0
70 40.0 14.0 to 70.7
100 60.0 20.0 to 100.0
200 120.0 40.0 to 200.0
90° 90.0 24.0 to 100.0
5* Nominal range
mm or angle °, ESC
Nominal valve travel or opening angle must be entered for nominal
(NOM) or substitute (SUb) initialization.
The possible adjustment range depends on the pin position from the
tableforCode4.
Indicatesmaximumtravel/anglereachedduringinitializationafter
initialization has been successfully completed.
6* Init mode
[MAX] Maximum range
NOM Nominal range
MAN Manual setting
SUb Emergency mode
ZP Zero calibration
ESC Stop
Select the initialization mode
MAX: Travel/angleoftheclosurememberfromtheCLOSED
position to the opposite stop in the actuator.
NOM: Travel/angleoftheclosuremembermeasuredfromthe
CLOSED position to the indicated OPEN position.
MAN: Manually selected range
SUb: Substitute calibration (without initialization)
7* w/x
[ää] Increasing/increas-
ing
äæ
Increasing/decreas-
ing
ESC
Directionofactionofthesetpointwinrelationtothetravel/anglex
Automatic adaptation:
AIR TO
OPEN:
On completing initialization, the direction of action
remainsincreasing/increasing(ää). A globe valve opens
as the set point increases.
AIR TO
CLOSE:
On completing initialization, the direction of action
changestoincreasing/decreasing(äæ). A globe valve
closes as the set point increases.