EB 8384-3 EN 15
Markings on the device
Positioner Type3730-3 x x x x x x x x 0 x 0 0 x 0 x x
Special application
Without 0
Device completely free of paint-impairing substances 1
Exhaust air with ¼ NPT connection, back of housing sealed 2
AttachmentaccordingtoVDI/VDE3847includinginterface 6
AttachmentaccordingtoVDI/VDE3847preparedforinterface 7
Special version
Without 0 0
IECEx Ex ia IIC T6...T4 Gb; Ex ia IIIC T80°C Db 1 1 2
Ex tb IIIC T80°C Db 5 3 4
Ex nA IIC T6 Gc, Ex tc IIIC T80°C Dc 8 1 3
EAC Ex On request 1 1 4
8 2 0
2.3 Firmware versions
Firmware revisions
Old New
1.01 1.10
The HART
®
protocol as per HART
®
specicationrevision5issupportedbydefault.The
HART
®
protocolcanbechangedtorevision6inTROVIS-VIEW.
The following status messages have been added:
• Code76–Noemergencymode
• Code77–Programloaderror
Reading indicates the number of zero calibrations performed since the last initialization.
Forinitializationof"AIRTOCLOSE"actuators,thedirectionofaction(Code7)isauto-
maticallysettoincreasing/decreasing.
Code3,theactivationperiodoftheenabledcongurationfunctionhasbeenextendedto
120s.
1.10 1.20
Electronics changed, no new functions added.
1.20 1.30
New EXPERTplus diagnostics functions (Code 48) added.
Positioner in EXPERTplus version with extended diagnostics features.
An initialization procedure in progress can be canceled by pressing the rotary pushbut-
ton.
The position transmitter (Code 37) and solenoid valve(Code45)optionsareautomati-
cally detected.