88 EB 8384-3 EN
Mounting and start-up
Thebusaddress/pollingaddresshastobe
within a range of 1 to 15.
Communication errors may occur when the
process controller/control station output is
not HART
®
-compatible.
Alternatively, a 250Ω resistor can be con-
nected in series and a 22µF capacitor can
be connected in parallel to the analog out-
put. The load for the controller output will in-
crease as a result.
Controller/control
station
Fig.35: Adapting the output signal
Note