EB 8384-4 EN 75
Start-up and settings
Default 126
Enable conguration:
Turn
g Code 3, display: No
Press
, Code 3 blinks.
Turn
YES
Press
, display:
Setting the bus address:
Turn
Code 46
Press
, Code 46 blinks.
Turn
Required bus address
Press
10 seconds The address is ad-
opted straightaway, provided that cyclic da-
ta exchange is not taking place. During the
cyclic data exchange, the newly set address
for the positioner is saved and adopted after
the cyclic data exchange is completed. The
newly assigned address is indicated in Code
46 in alternating sequence with the current
address. The new address is marked with 'n'
(new) and the currently used address with 'o'
(old).
The bus address can only be implemented by
the PROFIBUS command SET_ADDRESS
when the bus address is set to the default
setting [126]. Refer to Conguration Manual
uKH8384-4.
Note