DEVICE_MAN_ID (26)
Storage class: – · Read capability (r)
Manufacturer of the positioner
DEVICE_MESSAGE (37)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Any desired text. The text is saved in the field device.
• Max. 32 characters, [no text]
DEVICE_SER_NUM (28)
Storage class: – · Read capability (r)
Positioner’s serial number: Enables the clear identification of the field device in combination with de-
scriptions entered in DEVICE_MAN_ID and DEVICE_ID
DIAG_EVENT_SWITCH (44)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Classification of diagnostic and status alarms
DIAGNOSIS (29)
Storage class: – · Read capability (r)
Detailed information of the device, coded bitwise. More than one alarm possible at one time.
Alarms remain active as long as the event still exists (static alarms)
Bit: 0 = false · 1 = true
Byte Bit According to PA V3.01 Description
0 0 DIA_HW_ELECTR Hardware error in the electronics
0 1 DIA_HW_MECH Hardware error in the mechanics
02–
0 3 DIA_TEMP_ELECTR Temperature in the electronics too high
0 4 DIA_MEM_CHKSUM Checksum error in the data memory
0 5 DIA_MEASUREMENT Error occurred in measurement
0 6 DIA_NOT_INIT Device not initialized
0 7 DIA_INIT_ERR Initialization incorrect
1 0 DIA_ZERO_ERR Zero point error (end position)
11–
1 2 DIA_CONF_INVAL Configuration invalid/invalid address
1 3 DIA_WARMSTART Restart (warm start) performed
1 4 DIA_COLDSTART New start-up (cold start) performed
1 5 DIA_MAINTENANCE Maintenance required
1 6 DIA_CHARACT Invalid characteristic
1 7 IDENT_NUMBER_VIOLATION The ID number selected could not yet be
implemented by the device
40 KH 8384-4 EN
Physical Block, Slot 0 · Profile-specific parameters