SP (25)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Upper limit of the reference variable
Value and range from PV_SCALE ±10 %, [100 %]
Note: This value must be adapted correspondingly if the scale end setting is changed in PV_SCALE
parameter.
ST_REV (17)
Storage class: – · Read capability (r)
Revision level of static data
STRATEGY (19)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Grouping to allow faster processing of blocks
[0]
Blocks are grouped by entering the same value in the STRATEGY parameter of each block.
Note: These data are neither checked nor processed by the AO Function Block.
TAG_DESC (18)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Used to enter a user-selected text to identify and assign blocks.
Max. 32 characters, [no text]
TARGET_MODE (21)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Target mode of the positioner
8 · AUTO (automatic mode)
16 · MAN (manual mode)
128 · O/S (out of service)
KH 8384-4 EN 67
AO Function Block, Slot 1 · Profile-specific parameters