CHANNEL (30)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Connection of the Function Block with the Transducer Block
DI1: 0 · Not active
780 · Active
DI2: 0 · Not active
524 · Active
FSAFE_TYPE (36)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Fail-safe action
0 · FSAFE_VALUE is used as OUT_D
[1] · The last valid value of OUT_D is used
2 · OUT_D does not have a valid value
FSAFE_VAL_D (37)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Default value for OUT_D when the sensor/sensor electronics register an error
[0]
INVERT (31)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Inversion of the input value PV_D (from DI Transducer Block) before it is saved in the OUT_D parameter
[0] · Not inverted
1 · Inverted
MODE_BLK (22)
Storage class: – · Read capability (r)
Current mode
OUT_D* (26)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Output of the Function Block (only in MAN mode)
SIMULATE (40)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Simulation of input value PV_D; the DI Transducer Block and DI Function Block are separated (test)
94 KH 8384-4 EN
DI1/2 Function Block, Slot 2/3 · Profile-specific parameters