Fault/diagnostic alarm
Value (hex) Status alarm acc. to
Profile 3.01
Movement actuator impossible 0x80 GOOD_NON_SPECIFIC
Error solenoid valve 0x80 GOOD_NON_SPECIFIC
Function activated
Initialization active 0x80 GOOD_NON_SPECIFIC
Diagnostic function activated 0x80 GOOD_NON_SPECIFIC
14.4.2 Status alarms according to Profile 3.01 Condensed Status
Fault/diagnostic alarm
Default setting acc. to Pro
-
file 3.01 Condensed Status
Classified
Diagnosis
Yes No
Operational error
Device not initialized 0x24 BAD_MAINT_ALARM • DIA_INIT_ERR
Solenoid valve active 0x80 GOOD_NON_SPECIFIC • –
Total valve travel exceeded 0xA4 GOOD_MAINT_REQ • DIA_MAINTENANCE
Control loop error 0xA4 GOOD_MAINT_REQ • DIA_MAINTENANCE
Zero point error 0xA4 GOOD_MAINT_REQ • DIA_ZERO_ERR
Autocorrection 0x80 GOOD_NON_SPECIFIC •
DIA_MAINTENANCE
DIA_MEM_CHECKSUM
Fatal error 0x24 BAD_MAINT_ALARM • DIA_HW_ELECTR
Extended diagnostics available 0x80 GOOD_NON_SPECIFIC •
DIA_MAINTENANCE
EXTENSION_AVAILABLE
No emergency mode 0xA4 GOOD_MAINT_REQ • DIA_MEM_CHECKSUM
Temperature < –40 °C 0x80 GOOD_NON_SPECIFIC • –
Temperature > 80 °C 0x80 GOOD_NON_SPECIFIC • –
Initialization error
x > range 0xA4 GOOD_MAINT_REQ • DIA_INIT_ERR
Delta x < range 0xA4 GOOD_MAINT_REQ • DIA_INIT_ERR
Incorrect attachment
(mechanics/pneumatics)
0xA4 GOOD_MAINT_REQ
•
DIA_INIT_ERR
Initialization time exceeded 0xA4 GOOD_MAINT_REQ • DIA_INIT_ERR
Solenoid valve initialization 0xA4 GOOD_MAINT_REQ • DIA_INIT_ERR
Transit time too short 0xA4 GOOD_MAINT_REQ • DIA_INIT_ERR
Pin position 0xA4 GOOD_MAINT_REQ • DIA_INIT_ERR
Initialization running 0xA4 GOOD_MAINT_REQ • –
100 EB 8384-4 EN
PROFIBUS-PA communication