120 to 350 cm² actuators with 15 mm rated
travel.
For other actuator sizes or travels, select the
lever and pin position from the travel table
on page 15. Lever L and XL are included in
the mounting kit.
3. Place the lever (1) and disk spring (1.2)
on the sensor shaft.
Place the lever (1) in mid-position and
hold it in place. Screw on the nut (1.1).
4. Screw both bolts (14) to the bracket
(9.1) of the stem connector (9). Attach
the follower plate (3) and fix with the
screws (14.1).
5. Place the bracket with the sensor at the
NAMUR rib in such a manner that the
follower pin (2) rests in the slot of the fol-
lower plate (3), then screw the bracket
using its fixing screws onto the valve.
2.7.3 Mounting the position
sensor to Type 3510
Micro-flow Valve
For the required mounting parts as well as
the accessories, refer to the order numbers
listed in Tables 7 and 8 on page 45.
1. Place the lever (1) in mid-position and
hold it in place. Unscrew the nut (1.1)
and remove the standard attached lever
M (1) together with the disk spring (1.2)
from the sensor shaft.
2. Screw the position sensor (20) onto the
bracket (21).
3. Select the lever S (1) from the accesso
-
ries and screw the follower pin (2) into
the hole for pin position 17.
Place the lever (1) and disk spring (1.2)
on the sensor shaft.
Place the lever (1) in mid-position and
hold it in place. Screw on the nut (1.1).
4. Place the follower clamp (3) on the stem
connector, align it at a right angle and
screw tight.
5. Position the bracket (21) with the posi
-
tion sensor on the valve yoke and screw
tight, making sure the follower pin (2)
slides into the groove of the follower
clamp (3).
EB 8384-4 EN 43
Attachment to the control valve – Mounting parts and accessories