3.2 Electrical connections
The following standards apply to in
-
stallations in hazardous areas:
EN 60079-14: 2008 (VDE 0165
Part 1) Explosive atmospheres -
Electrical installations design, selec
-
tion and erection.
NOTICE
The terminal assignment must be ad
-
hered to. Reversing the assignment of the
electrical terminals may cause the explo
-
sion protection to become ineffective!
Do not loosen enameled screws in or on
the housing.
For the interconnection of intrinsically
safe electrical equipment, the permissible
maximum values specified in the EC type
examination certificate apply (U
i
or U
o
,
I
i
or I
o
, P
i
or P
o
, C
i
or C
o
and L
i
or L
o
).
Note on the selection of cables and wires:
To install intrinsically safe circuits, observe
Clause 12 of EN 60079-14: 2008
(VDE 0165 Part 1).
To run multi-core cables or lines with more
than one intrinsically safe circuit, clause
12.2.2.7 of this standard applies.
Especially for commonly used insulating ma
-
terials, such as polyethylene, the radial
thickness of the conductor insulation must
have a minimum thickness of 0.2 mm. The
diameter of a single wire of a flexible con
-
ductor must not be smaller than 0.1 mm.
Protect the conductor ends against splicing,
e.g. by using wire-end ferrules.
When two separate cables are used for con
-
nection, an additional cable gland can be
installed.
Seal cable entries left unused with blanking
plugs.
Devices used at ambient temperatures be
-
low –20 °C must be fitted with metal cable
glands.
Equipment for use in zone 2/zone 22
In equipment operated with type of protec
-
tion Ex nA II (non-sparking apparatus), the
standard EN 60079-15: 2003 specifies that
circuits may be connected, interrupted or
switched while energized only during instal-
lation, maintenance or repair.
For equipment connected to energy-limited
circuits with type of protection Ex nL (en-
ergy-limited apparatus), the standard
EN 60079-15: 2003 allows this type of
equipment to be switched under normal op-
erating conditions.
For the interconnection of equipment to en
-
ergy-limited circuits with type of protection
Ex nL IIC, the permissible maximum values
specified in the statement of conformity
apply.
Cable entry
The cable entry with M20 x 1.5 cable gland,
6 to 12 mm clamping range.
There is a second M20 x 1.5 threaded bore
in the housing that can be used for addi
-
tional connection, when required.
The screw terminals are designed for wire
cross-sections of 0.2 to 2.5 mm² (tightening
torque of screws 0.5 to 0.6 Nm).