The positioner switches to automatic oper
-
ating mode!
The current valve position is indicated in %.
Note: If the positioner shows a tendency to
oscillate in automatic operating mode, the
parameters K
P
and T
V
must be slightly cor
-
rected. Proceed as follows:
Set T
V
to 4 (Code 18).
If the positioner still oscillates, the gain K
P
(Code 17) must be decreased until the
positioner shows a stable behavior.
Zero point calibration
Finally, if process operations allow it, the
zero point must be adjusted according to
section 5.8 on page 71.
CAUTION!
The positioner automatically moves to zero
point.
5.7 Fault/failure
All status and fault alarms are assigned a
classified status in the positioner.
To provide a better overview, the classified
alarms are summarized in a condensed sta
-
tus for the positioner (see section 6).
The condensed status appears on the display
with the following icons:
Condensed status Display
Maintenance alarm
Maintenance required/
Maintenance demanded
Function check Text
No message
If the positioner has not been initialized, the
diagnostic alarm “Device not initialized” is
generated. The symbol appears on the
display as the positioner cannot follows its
reference variable.
To access the error codes, turn the but
-
ton past the Code
50.
Err appears on the display with the respec
-
tive error code.
For the cause of the fault and the recom-
mended action, refer to the codes listed in
section 15.1 on page 111 onwards.
Display indicating an
error code
After an error code has occurred, you
should first try to confirm it as follows:
Enable configuration:
Turn
→
Code 3 , press ,
turn
→
ON, press .
Turn until the error code number ap
-
pears, then press to confirm it.
Should the error occur again, read the rem
-
edy instructions in the error code list.
Occurrences such as when the total valve
travel is exceeded or when the temperature
70 EB 8384-4 EN
Start-up and settings