1. Change the bus address of Type 3730-4 to the same bus address as Type 3785. This
can be done over PROFIBUS (DEVICE_ADDRESS parameter), using TROVIS-VIEW
configuration and operator interface or in Code 46 in the positioner.
2. Put positioner into operation (see section 5).
Note: After initialization (in step 2), the positioner is in compatibility (adaptation) mode
(IDENT_NUMBER_SELECTOR parameter in the Physical Block). Do not change this setting.
14.2.2 Data exchange
The relationship between output and input is based on the control system/master class 1.
SLOT 1
Version 1: Module = SP
0x4A or 0x82, 0x84, 0x08, 0x05
Output
Byte 0 1 2 3 4
Octet 1
Sign,
Exponent
Octet 2
Exponent
Fraction
Octet 3
Fraction
Octet 4
Fraction
Octet 5
Fraction
SP, value
(Floating Point, IEEE)
Status
4
Version 2: Module = RCAS_IN, RCAS_OUT
0xC4, 0x84, 0x84, 0x08, 0x05, 0x08, 0x05
Output
Byte 0 1 2 3 4
Octet 1
Sign,
Exponent
Octet 2
Exponent
Fraction
Octet 3
Fraction
Octet 4
Fraction
Octet 5
Fraction
RCAS_IN, value
(Floating Point, IEEE)
Status
EB 8384-4 EN 89
PROFIBUS-PA communication