4.6 Attaching an external
position sensor
Refer to Table 6 on p. 43 for the mounting
parts as well as the accessories required.
In the positioner version with an external
position sensor, the sensor placed in a sepa
-
rate housing is attached over a plate or
bracket to the control valve. The travel
pick-off corresponds to that of a standard
device.
The positioner unit can be mounted as re
-
quired to a wall or a pipe.
For the pneumatic connection either a con
-
necting plate (6) or a pressure gauge
bracket (7) must be fixed to the housing, de
-
pending on the accessory chosen. Make
sure the seal rings (6.1) are correctly in
-
serted (see Fig. 6, bottom right).
For the electrical connection a 10 meter
connecting lead with M12x1 connectors is
included in the scope of delivery.
Note:
In addition, the instructions in sections
5.1 and 5.2 apply for the pneumatic and
electrical connection.
Operation and setting are described in
sections 6 and 7.
Since 2009, the back of the position sen
-
sor (20) is fitted with two pins acting as
mechanical stops for the lever (1). If this
position sensor is mounted using old
mounting parts, two corresponding Ø
8 mm holes must be drilled into the
mounting plate/bracket (21).
4.6.1 Mounting the position
sensor with direct
attachment
Type 3277-5 Actuator with 120 cm²
The signal pressure from the positioner is
routed over the signal pressure connection
of the connecting plate (9, Fig. 14 left) to the
actuator diaphragm chamber. To proceed,
first screw the connecting plate (9) included
in the accessories onto the actuator yoke.
4
Turn the connecting plate (9) so that the
correct symbol for the fail-safe position
"Actuator stem extends" or "Actuator
stem retracts" is aligned with the mark
-
ing (Fig. 14, below).
4
Make sure that the gasket for the con
-
necting plate (9) is correctly inserted.
4
The connecting plate has boreholes with
NPT and G threads.
Seal the threaded connection that is not
used with the rubber seal and square
plug.
Type 3277 Actuator with 240 to 700 cm²:
The signal pressure is routed to the connec
-
tion at the side of the actuator yoke for the
version "Actuator stem extends".
For the fail-safe position "Actuator stem re
-
34 EB 8384-5 EN
Attachment to the control valve Mounting parts and accessories
Fig. 13 · Positioner unit with sensor mounted on a
micro-flow valve

Table of Contents