Samson 3730-5 - MAX - Initialization Based on Maximum Range

Samson 3730-5
208 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Valve closed
position
Direction of
action
Reference variable
Valve
Closed at Open at
AIR TO OPEN ää 0 % 100 %
AIR TO CLOSE äæ 100 % 0 %
The tight-closing function is activated.
NOTICE
Set Code 15 (final position w>) to 99 % for
three-way valves.
Canceling an initalization process
The initialization procedure can be canceled
while running by pressing the rotary
pushbutton ( ). StOP appears three sec-
onds long and the positioner then changes
to the fail-safe position (SAFE).
Exit the fail-safe position again over Code 0
(see section 8.2.2).
7.6.1 MAX – Initialization based
on maximum range
The positioner determines travel/angle of
rotation of the closing member from the
CLOSED position to the opposite side and
adopts this travel/angle of rotation as the
operating range from 0 to 100 %.
Enable configuration:
Note: If no settings are entered within
120 seconds, the enabled configuration
function becomes invalid.
Default
OFF
Turn
Code
3
, display:
OFF
Press
Code
3
blinks
Turn
ON
Press , display
Select the initialization mode:
Initialization mode
Default
MAX
Turn
Code
6
Press
Turn
MAX
Press to confirm the
MAX
as the initial-
ization mode.
Start initialization:
4
Press INIT key to start initialization!
The nominal travel/angle of rotation is indi
-
cated in % after initialization. Code
5
(nomi
-
nal range) remains locked. The parameters
for travel/angle range start (Code
8
) and
travel/angle range end (Code
9
) can also
only be displayed and modified in %.
For a reading in mm/°, enter the pin posi
-
tion (Code
4
).
EB 8384-5 EN 57
Start-up Settings

Table of Contents