Code
no.
Parameter – Display, values
[default setting]
Description
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
4*
Pin position
17, 25, 35, 50, 70, 100,
200 mm
90° with rotary actuators
[OFF], ESC
Note! If you select a pin
position in Code 4 that is too
small, the positioner switches
to SAFE mode for reasons of
safety
The follower pin must be inserted into the correct pin position ac
-
cording to the valve travel/angle of rotation.
For initialization using NOM or SUb, this pin position must be
entered.
Pin position Standard Adjustment range
Code 4 Code 5 Code 5
17 7.5 3.6 to 17.7
25 7.5 5.0 to 25.0
35 15.0 7.0 to 35.4
50 30.0 10.0 to 50.0
70 40.0 14.0 to 70.7
100 60.0 20.0 to 100.0
200 120.0 40.0 to 200.0
90° 90.0 24.0 to 100.0
5*
Nominal range
mm or angle °
ESC
For initialization using NOM or SUb, the nominal travel/angle of
rotation of the valve must be entered.
The permissible adjustment range depends on the pin position
according to the table for Code 4.
Code 5 is generally locked until Code 4 is set to OFF, i.e. after a
pin position has been entered, Code 5 can be configured.
After initialization has been successfully completed, the maximum
nominal travel/angle reached on initialization is displayed.
6*
Init mode
[MAX]
NOM
MAN
SUb
ZP
ESC
Select the initialization mode
MAX: Travel/angle of the closure member from the CLOSED
position to the opposite stop in the actuator.
NOM: Travel/angle of the closure member measured from the
CLOSED position to the indicated OPEN position.
MAN: Manually selected range
SUb: Substitute calibration (without initialization)
ZP: Zero calibration
EB 8384-5 EN 91