EB 8384-3 EN 7-11
Start-up and conguration
7.5.3 MAN – Initialization based on a manually selected OPEN
position
Before starting initialization, move the control valve manually to the OPEN position. Turn the
rotary pushbutton ( ) clockwise in small steps. The valve must be moved with a monotoni-
callyincreasingsignalpressure.Thepositionercalculatesthedifferentialtravel/anglefrom
the OPEN and CLOSED positions and adopts it as the operating range with limits of lower
travel/anglerangevalue(Code8)anduppertravel/anglerangevalue(Code9).
Enable conguration:
Congurationislockedagainifnosettingsareenteredwithin120seconds.
1. Turn untilCode3appears(reading:
No).
2. Press , the code number 3 blinks.
3. Turn until YES appears.
4. Press toconrm(reading: ).
Enableconguration
Default: No
Enter the pin position:
1. Turn untilCode4appears.
2. Press , the code number 4 blinks.
3. Turn to select pin position on lever (see
relevant section on attachment).
4. Press toconrm.
mm
Pin position
Default: No
Select the initialization mode:
1. Turn untilCode6appears.
2. Press , the code number 6 blinks.
3. Turn until MAN appears.
4. Press toconrmtheMANinitialization
mode.
Init mode
Default: MAX