EB 8384-3 EN 16-7
Code
no.
Parameter–Readings/
values [default setting]
Description
28* Alarm test
Reading direction:
Standard Turned
[No] [No]
RUN 1 1 RUN
RUN 2 2 RUN
RUN 3 3 RUN
ESC ESC
Test of software limit switch alarms A1 and A2 as well as of fault
alarm contact A3.
Ifthetestisactivated,thecontactisswitchedvetimes.
RUN1/1RUN:softwarelimitswitchA1to≥2.2mA
RUN2/2RUN:softwarelimitswitchA2to≥2.2mA
RUN3/3RUN:faultalarmcontactA3to≤1.0mA
29* Position transmitter x/ix
3)
[ää], äæ, ESC
Operating direction of the position transmitter: it indicates assign-
mentbetweentravel/anglepositionandoutputsignalibasedon
CLOSED position.
Theoperatingrange(seeCode8)ofthevalveisrepresentedbythe
4to20mAsignal.Valuesexceedingorfallingbelowthelimits2.4
and21.6mAcanbeindicated.
Whenthepositionerhasnotbeenmounted(setpointsmallerthan
3.6mA),thesignalis0.9mAand3.8mAthepositionerhasnot
beeninitialized.WhenYESissetinCode32,thepositiontransmit-
terissuesthevalueasperCode30duringinitializationorzerocali-
bration.WhenNoissetinCode32,4mAisissuedduringarun-
ning calibration.
30* Fault alarm ix
3)
HI, LO, [No], ESC
Select if and how alarms that cause the fault alarm contact to be
switched are also indicated by the position transmitter.
HIix=21.6±0.1mAorLOix=2.4±0.1mA
31* Position transmitter test
3)
–10.0to110.0%ofthe
operating range, [default
value is last indicated val-
ue of the position transmit-
ter], ESC
Testingthepositiontransmitter.Valuescanbeenteredinrelationto
the operating range.
The momentary valve position is used in initialized positioners local-
lyasthestartvalue(bumplesschangeovertothetestmode).When
testing by software, the entered simulation value is issued as the po-
sition feedback signal for 30 seconds.
3)
Analogpositiontransmitter:Code29/30/31canonlybeselectedifthepositiontransmitter(optional)isinstalled.