EasyManua.ls Logo

Samson 3730 Series - Error codes

Samson 3730 Series
216 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16-10 EB 8384-3 EN
16.1.1 Error codes
Initialization errors
Error codes –
Recommended action
Condensed state message active, when prompted, Err appears.
Whenfaultalarmsexist,theyaredisplayedhere.
50 x > permissible
range
Valueofmeasuringsignaltoohighortoolow;theleveroperatesnearits
mechanical stops.
Pin not mounted properly
Bracket slipped in case of NAMUR attachment or positioner is off center.
Follower plate not mounted properly.
Status
classication
[Maintenance required]
Recommended
action
Check attachment and pin position, set operating mode from SAFE to MAN
and re-initialize the positioner.
51 Δx < permissible
range
Insufcientmeasuringspanofthelever.
Pin not mounted properly
Wronglever
Anangleofrotationsmallerthan16°atthepositionershaftonlygenerates
analarm.Ananglebelow9°leadstotheinitializationbeingcanceled.
Status
classication
[Maintenance required]
Recommended
action
Check attachment and re-initialize the positioner.
52 Attachment Invalid positioner attachment
Ratedtravel/angle(Code5)couldnotbeachievedduringNOM
initialization (no tolerance downwards permissible).
Mechanical or pneumatic fault, e.g. wrong lever selected or supply pressure
too low to move to the required position.
Status
classication
[Maintenance required]
Recommended
action
Check attachment and supply pressure. Re-initialize the positioner.
Undercertaincircumstances,itmaybepossibletocheckthemaximumtravel/
angle by entering the actual pin position and then performing a MAX
initialization.
After initialization has been completed, the Code 5 indicates the maximum
achieved travel or angle.

Table of Contents

Other manuals for Samson 3730 Series

Related product manuals