EB 8384-3 EN 5-11
Installation
Î Make sure that the vent plug is locat-
ed at the bottom when the control
valve is installed to allow any con-
densed water that collects to drain
off.
5.5.2 Attachment according to
IEC60534-6
Î See Fig.5-7
Î Required mounting parts and accesso-
ries: Table 5-7
Î Observethetraveltableonpage5-5.
The positioner is attached to the control valve
using a NAMUR bracket (10).
1. Screw the two bolts (14) to the bracket
(9.1) of the stem connector (9), place the
follower plate (3) on top and use the
screws (14.1) for fastening.
Actuator sizes 2800cm² and 1400cm²
with 120mm travel:
− For a travel of 60 mm or smaller,
screw the longer follower plate (3.1)
directly to the stem connector (9).
− Foratravelexceeding60mm,mount
thebracket(16)rstandthenthefol-
lower plate (3) to the bracket togeth-
er with the bolts (14) and screws
(14.1).
2. Mount NAMUR bracket (10) to the con-
trol valve as follows:
− For attachment to the NAMUR rib,
useanM8screw(11)andtoothed
lock washer directly in the yoke hole.
− For attachment to valves with rod-
type yokes, use two U-bolts (15)
around the yoke. Align the NAMUR
10
11
1
1
14.1
3
3.1
16
15
14
1
1.2
1.1
2
9.1
9
6.1 6 7 8
Attachment to rod-type yoke
Rodswith20to35mmdiameter
Attachment to NAMUR rib
Additional bracket for
actuators with
2800cm²andtravel≥
60mm
XL and L lever
1 Lever
1.1 Nut
1.2 Disk spring
2 Follower pin
3 Follower plate
3.1 Follower plate
6 Connecting plate
6.1 Seals
7 Pressure gauge
bracket
8 Pressure gauge
mounting kit
9 Stem connector
9.1 Bracket
10 NAMUR bracket
11 Screw
14 Bolt
14.1 Screws
15 U-bolt
16 Bracket
Fig.5-7: Attachment according to IEC60534-6 (NAMUR)