EasyManua.ls Logo

Samson Series 3730 - Technical Data

Samson Series 3730
216 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EB 8384-3 EN 3-5
Design and principle of operation
3.5 Technical data
Table 3-1: Type3730-3 Electropneumatic Positioner
Type3730-3 Positioner
The technical data for the explosion-protected devices may be restricted by the
limits specied in the test certicates.
Valve
travel
Adjustable
DirectattachmenttoType3277Actuator 3.6to30mm
AttachmentaccordingtoIEC60534-6
(NAMUR)
3.6to300mm
AttachmentaccordingtoVDI/VDE3847 3.6to300mm
Attachmenttorotaryactuators(VDI/
VDE3845)
24to100°openingangle
Travel
range
Adjustable
Adjustablewithintheinitializedtravel/angleofrotationofthevalve;travelcanbe
restrictedto1/5atthemaximum.
Set point
w
Signal range 4to20mA·Two-wiredevice,reversepolarityprotection·Minimumspan4mA
Static destruction
limit
100mA
Minimum current 3.6mAfordisplay·3.8mAforoperation
Load impedance ≤8.2V(correspondsto410Ωat20mA)
Supply
Supply air 1.4to7bar(20to105psi)
Air quality acc. to
ISO8573-1
Max. particle size and density: Class 4 · Oil content: Class 3 · Pressure dew point:
Class 3 or at least 10 K below the lowest ambient temperature to be expected
Signal pressure (output)
0baruptothesupplypressure·Canbelimitedto1.4bar/2.4bar/3.7bar
±0.2barbysoftware
Charac-
teristic
Adjustable
Linear/Equalpercentage/Reverseequalpercentage
User-dened(overoperatingsoftwareandcommunication)
Butteryvalve,rotaryplugvalveandsegmentedballvalve:Linear/equalpercent-
age
Deviation ≤1%
Hysteresis ≤0.3%
Sensitivity ≤0.1%
Transit time Exhaustandsupplyadjustableseparatelyupto240sbysoftware
Direction of action Reversible
Air consumption, steady state Independentofsupplyairapprox.110l
n
/h
Air out-
put ca-
pacity
Actuator (supply) AtΔp=6bar:8.5m
n
³/h·AtΔp=1.4bar:3.0m
n
³/h·K
Vmax(20°C)
=0.09
Actuator (exhaust) AtΔp=6bar:14.0m
n
³/h·AtΔp=1.4bar:4.5m
n
³/h·K
Vmax(20°C)
=0.15
Permissible ambient temperature
–20to+80°C All versions
–45to+80°C Withmetalcablegland
–55to+80°C Special version for low temperatures with metal cable gland
(Type3730-3xxxxxxxx0x02x0xx)
The temperature limits for the explosion-protected devices may be restricted by
the limits specied in the test certicates.