EasyManua.ls Logo

Samson TROVIS 3730-1 - 3.7 Technical data

Samson TROVIS 3730-1
108 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EB 8484-1 EN 23
Design and principle of operation
3.7 Technical data
Table11: TROVIS3730-1 Electropneumatic Positioner
Travel
Adjustable travel for
Direct attachment to Type 3277: 3.5to30mm
AttachmentaccordingtoIEC60534-6(NAMUR): 3.5to300mm
AttachmentaccordingtoVDI/VDE3847 3.5to300mm
Attachment to rotary actuators: 24to100°
Travel range Adjustablewithintheinitializedtravel/angleofrotationofthevalve;travel
canberestrictedto1/5atthemaximum.
Set point w
Signal range 4to20mA·Two-wiredevice,reversepolarityprotection
Split-rangeoperation:4to11.9mAand12.1to20mA
Static destruction limit ±33V
Minimum current 3.6mAfordisplay·3.8mAforoperation
Load impedance Noexplosionprotection:≤6.6V(correspondingto330Ωat20mA)
Explosionprotection:≤7.3V(correspondingto365Ωat20mA)
Supply air
Supply air 1.4to7bar(20to105psi)
Air quality acc. to
ISO8573-1
Max. particle size and density: Class 4
Oil content: Class 3
Pressure dew point: Class 3 or at least 10 K below the low-
est ambient temperature to be expected
Signal pressure (output) 0baruptothesupplypressure·Canbelimitedto2.4bar±0.2barby
software
Hysteresis ≤0.3%
Sensitivity ≤0.1%
Characteristic Linear/equalpercentage/reverseequalpercentage/SAMSONbuttery
valve/VETECrotaryplugvalve/segmentedballvalve
Direction of action Reversible
Air consumption, steady
state
Independentofsupplyairapprox.65l
n
/h
Airoutputcapacity(when∆p=6bar)
Tollactuatorwithair 8.5 m
n
³/h·AtΔp=1.4bar:3.0m
n
³/h·K
Vmax(20°C)
=0.09
To vent actuator 14.0 m
n
³/h·AtΔp=1.4bar:4.5m
n
³/h·K
Vmax(20°C)
=0.15