78 EB 8484-1 EN
Operating the positioner
8.1 Enabling conguration to change parameters
Beforechangingparametersettingsinaninitializedpositioner,congurationmustbeen-
abledrstbyselectingCodeP2:
LOCK and the key icon indicate that the conguration is locked. De-
activate locking as follows:
1. Turn until CodeP2 appears.
2. Press
to conrm the selected code. P2 blinks.
3. Turn
until OPEN appears.
4. Press
to deactivate the locking.
Conguration is locked again if no settings are entered within 5 min.
8.2 Saving parameters in a non-volatile memory
Changed parameters are indicated by the icon on the display. To save changes to pa-
rameters in a non-volatile memory, proceed as follows:
1. After changing a parameter, turn until the reading jumps from Code P27 to Code
P0 (or from Code P0 to Code P27).
Î The icon disappears. The changes to a parameter are saved in a non-volatile mem-
ory.
8.3 Entering the fail-safe position
Denethefail-safepositionofthevalvetakingthevalvetypeandtheactuator'sdirectionof
action into account.
Fail-safe position Description
ATO (air to open) setting: Signal pressure opens the valve, e.g. for a fail-
close valve
ATC (air to close) setting: Signal pressure closes the valve, e.g. for a fail-
open valve
Note