28
Installation Procedure
Installation Procedure
English
Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
Function Page Use of external control
Setting the output of
external control
S-Plasma ion Buzzer control
Maximum filter usage
time
Indication
and details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
2
0 Disuse
Slave,
Existing
Control
0
Thermo
on
0 Disuse 0 Use of buzzer 2 1000 hours
1 On/Off
2 Off
3 Window
4 Disuse
Master,
Existing
Control
5 On/Off
6 Off
7 Window
8 Disuse
Slave,
Reverse
Control
1
Operation
on
1 Use 1 Disuse of buzzer 6 2000 hours
9 On/Off
A Off
B Window
C Disuse
Master,
Reverse
Control
D On/Off
E Off
F Window
Option SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
Function Page
Individual control with
remote control
Heating setting
compensation
Reserved Reserved Reserved
Indication
and details
Indication Details Indication Details Indication Details
3
0 or 1 Indoor 1 0
0
°C
(default)
2 Indoor 2 1 2°C
3 Indoor 3
2 5°C
4
Indoor 4
• Even if you set the Use of drain pump (SEG8) option to 0, it is automatically set to 2 (the drain pump is used with 3
minute delay).
• If you set the Maximum filter usage time (SEG18) option to a value other than 2 and 6, it is automatically set to 2
(1000 hours).
• If you set the Individual control with remote control (SEG20) option to a value other than 0 to 4, it is automatically set
to 0 (Indoor 1).
• Each model's compensation of the wind-free fan RPM (SEG11) option has to be set by default.
• Compensation of the wind-free fan RPM (SEG11) option adjusts 20 rpm per 1 step.
* Level control: The centralized controller can limit the functions and inputs of connected products with this
function enabled. Example: Operation mode limit (Cooling only/Heating only/No limitation), Heating
temperature upper limit, Cooling temperature lower limit) To enable ‘Level controlwhen applying the
DPM with the centralized controller, appoint the master (Set ‘Use of external control [SEG14] option to 4
or higher).
CAC R-32_Mini 4way_IM_DB68-08129A-00_EN_20181115.indd 28 2018/11/15 13:49:34