6. Capacity Correction
90
Outdoor Units
AC052/060MXADKH/EU
Cooling
Pipe Length (m)
5 10 15 20 25 30
Level Difference (m)
30 - - - - - -
25 - - - - - -
20 - - - 92 90
15 - - 94 92 90
10 - 96 94 92 90
5 98 96 94 92 90
0 100 98 96 94 92 90
-5 97 95 93 91 89
-10 - 94 93 91 89
-15 - - 92 90 88
-20 - - - - 89 86
-25 - - - - - -
-30 - - - - -
Heating
Pipe Length (m)
5 10 15 20 25 30
Level Difference (m)
30 - - - - - -
25 - - - - - -
20 - - - - 94 92
15 - - - 95 94 92
10 - - 97 95 94 92
5 - 98 97 95 94 92
0 100 98 97 95 94 92
-5 - 98 97 95 94 92
-10 - - 97 95 94 92
-15 - - - 95 94 92
-20 - - - - 94 92
-25 - - - - - -
-30 - - - - - -