4-38 Samsung Electronics
With its phase control motor, you can adjust the indoor unit fan speed depending on the installation condition.
If the external static pressure is high so that the duct becomes longer or if the external static pressure is low so that
the duct becomes shorter, adjust the fan speed by referring the following table.
E. S. P(External Static Pressure) setting for phase control motor
• represents E. S. P(External Static Pressure) range of factory setting.
You don’t have to adjust the fan speed separately if the external static pressure of the installation place is in
. When it is out of
, input the appropriate option code.
•
If you input the inappropriate option code, error may occur or the air conditioner is out of order. The
option code must be inputted correctly by the installation specialist or service agent.
Model
AC200KNHPKH AC250KNHPKH
Static Pressure(mmAq)
Option code for indoor unit
5≤ESP<7.5 011074-1C50C0-27C8E6-372000 011074-1C50F0-270014-373800
7.5≤ESP<10 011074-1C50E3-27C8E6-372000 011074-1C50F3-270014-373800
10≤ESP<12.5 011074-1C50F5-27C8E6-372000 011074-1C5435-270014-373800
12.5≤ESP<15 011074-1C5436-27C8E6-372000 011074-1C5466-270014-373800
15≤ESP<17.5 011074-1C5458-27C8E6-372000 011074-1C5487-270014-373800
17.5≤ESP≤20 011074-1C548E-27C8E6-372000 011074-1C54BB-270014-373800
•
If the coil is not dry, run the unit for 2 hours with fan only to dry the coil.
•
The air filter is properly attached into the air passage on the air suction side of the air conditioning unit.
•Adjust the dampers so that each air inlet and outlet exhusts the designed airow rate.
•If using booster fans(an outdoor air processing unit or ERV via duct), do not use Automatic Air-Volume function.
•If the duct congurations have been changed, automatic air-volume function perform again.
•Theproductcanbeusedwithintherangeofratedvoltage220V/230V/240V±5V.Iftheproductneedstobe
installed in the condition that is out of the rated voltage stated above, additional setting with installation option is
required.