EasyManua.ls Logo

Samsung AE044MXTPEH - Combination and Connection Ratio limitation

Samsung AE044MXTPEH
127 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
General Overview
12
Samsung Electronics
2-3 Combination and Connection Ratio limitation
Outdoor unit
Cooling
capacity (kW)
Maximum allowable
connections for indoor units
(Not including Hydro-A2W)
Total capacity of
connected indoor units
(kW)
AE044MXTPEH
4.4 2 2.2~4.4
AE066MXTPEH
6.6 3 3.3~6.6
AE090MXTPEH
9 4 4.5~9.0
AE120MXTPEH
12 5 6.0~12.0
AE160MXTPEH
16 7 8.0~16.0
AE090MXTPGH
9 4 4.5~9.0
AE120MXTPGH
12 5 6.0~12.0
AE160MXTPGH
16 7 8.0~16.0
• Available for max 7 indoor units.
• When considering the system capacity of allowable indoor units, follow the table above.

Table of Contents

Related product manuals