EasyManua.ls Logo

Samsung AM200FXWANR - Page 228

Samsung AM200FXWANR
295 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Piping Diagram
Samsung Electronics 227
High Pressure Protection
ƒ Purpose
Prevent abnormal high pressure to protect the system and compressors.
ƒ Concept
The compressor operation frequency is lowered to decrease the high pressure.
ƒ Control specifications in detail
- The compressor operation frequency is controlled according to the
high pressure, as shown below.
1st step Hz hold: The current frequency is fixed. (It is possible to lower the frequency if necessary)
2nd ste
p Hz down: The frequency is forcibly lowered by 5Hz at specified intervals.
3rd step HP down: The frequency is forcibly lowered by 1Hz every second.
4th step Comp trip: Compressors stop and an error is triggered (E407).
Compressor Trip (E407)
High Pressure < 30 k gf /cm
2
,g : Compressor Trip release
Hz Hold area
Hz Down area
HP Down area
Normal op eration
Hz Hold release
Hz Down release
HP Down release
Compressor Trip (E407)
High Pressure < 30 k gf /cm
2
,g : Compressor Trip release
Hz Hold area
Hz Down area
HP Down area
Normal op eration
Hz Hold release
Hz Down release
HP Down release
T.HP = Target High Pressure
36
37
38
40
High Pressure (k gf /cm
2
,g )
32
& (T .HP + 4)
40
High Pressure (k gf /cm
2
,g )
30
& (T .HP + 3)
28
& (T.HP + 1.5)
Cooling
Heating
7-3 Functions (cont.)
7-3-2-5 Protective control
7-3-2 Control (cont.)

Table of Contents

Related product manuals