10. Capacity Correction
50
Quantum 2.0 : RNS18YBT+RXS18YBT (AR18TSFYBWKNCV+AR18TSFYBWKXCV),
RNS24YBT+RXS24YBT (AR24TSFYBWKNCV+AR24TSFYBWKXCV)
Max Heat 2.0 : RNS18ABT+RXS18ACT (AR18TSFABWKNCV+AR18TSFACWKXCV),
RNS24ABT+RXS24ACT (AR24TSFABWKNCV+AR24TSFACWKXCV)
Wind-Freeā„¢ 2.0 : RNS18ABT+RXS18ABT (AR18TSFABWKNCV+AR18TSFABWKXCV),
RNS24ABT+RXS24ABT (AR24TSFABWKNCV+AR24TSFABWKXCV)
Cooling
Pipe Length (ft)
16 33 41 49 66 82 98
Level Difference (ft)
66 -----0.870.85
49 - - - 0.92 0.9 0.88 0.86
33 - 0.95 0.94 0.93 0.91 0.89 0.87
23 - 0.96 0.95 0.94 0.92 0.9 0.88
16 0.99 0.97 0.96 0.95 0.93 0.91 0.89
0 1 0.98 0.97 0.96 0.94 0.92 0.9
-16 0.99 0.97 0.96 0.95 0.93 0.91 0.89
-23 - 0.96 0.95 0.94 0.92 0.9 0.88
-33 - 0.95 0.94 0.93 0.91 0.89 0.87
-49 - - - 0.92 0.9 0.88 0.86
-66 -----0.870.85
Heating
Pipe Length (ft)
16 33 41 49 66 82 98
Level Difference (ft)
66 -----0.870.85
49 - - - 0.92 0.9 0.88 0.86
33 - 0.95 0.94 0.93 0.91 0.89 0.87
23 - 0.96 0.95 0.94 0.92 0.9 0.88
16 0.99 0.97 0.96 0.95 0.93 0.91 0.89
0 1 0.98 0.97 0.96 0.94 0.92 0.9
-16 0.99 0.97 0.96 0.95 0.93 0.91 0.89
-23 - 0.96 0.95 0.94 0.92 0.9 0.88
-33 - 0.95 0.94 0.93 0.91 0.89 0.87
-49 - - - 0.92 0.9 0.88 0.86
-66 -----0.870.85
Outdoor units