9
2. Specification
Type PAC( for Iran) PAC( for Iran)
Model Name
Indoor Unit AF50MV3MCEENHC AF50MS3MCEENHC
Outdoor Unit AF50MV3MCEEXHC AF50MS3MCEEXHC
Indoor Unit
Casing Material - ABS ABS
Drain Pump Drain Pump - - -
Max. lifting Height / Displacement mm / Liter/h - -
Additional
Accessories
Drain Pump External Model - - -
Internal Model - - -
Max. lifting Height /
Displacement
mm / Liter/h - -
Air Filter - - -
Virus Doctor - - -
Outdoor Unit
Power Supply Ø, #, V, Hz 3,4,380-415,50 3,4,380-415,50
Heat
Exchanger
Type - Fin & Tube Fin & Tube
Material Fin - AL AL
Tube - CU CU
Fin Treatment - - -
Compressor Model Name UG5TK1450FJX UG5TK1450FJX
Type - Twin BLDC Rotary Twin BLDC Rotary
Output kW 4.19 4.19
Oil
Type - POE POE
Initial charge cc 1,700 1,700
Fan
Type - Propellar Propellar
Discharge direction - Front Front
Quantity EA 2 2
Air Flow Rate
CMM 110 110
l/s 1,833 1,833
Fan Motor
Type - BLDC BLDC
Output W x n 125 x 2 125 x 2
Sound
Sound Pressure Level
Cooling dB(A) 53 53
Heating dB(A) - 54
Sound Power Level dB(A) - -
External
Dimension
Net Weight kg 84.5 85.0
Shipping Weight
Net Dimensions (WxHxD)
kg 93.5 94.0
mm 940 x 1210 x 330 940 x 1210 x 330
inch 37 x 47 5/8 x 13 37 x 47 5/8 x 13
Shipping Dimensions (WxHxD)
mm 995 x 1388 x 426 995 x 1388 x 426
inch 39 3/16 x 54 5/8 x 16 3/4 39 3/16 x 54 5/8 x 16 3/4
Casing Material Body - EGI steel plate EGI steel plate
Operating
Temp. Range
Cooling ℃ (℉)
Heating ℃ (℉) -
NOTE
• Specification may be subject to change without prior notice.
1) Capacities are based on (Equivalent refrigerant piping 5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Select wire size based on the value of MCA
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level based on T1 condition (Indoor temperature 27°C DB, 19°C WB / Outdoor
temperature : 35°C DB, 24°C WB)
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
5) hese products contain R410A which is fluorinated greenhouse gas.