SAMWON ENG SU-105 Instrument for Automatic Control of Temperature Page 1/4
Instruction Manual of Instrument for Automatic Control of
Temperature SU-105
Model
Kinds of Sensor
Output
SU-105KRR
K (-200.0~999.0)
OUT1,2:RELAY
SU-105PRR
Pt100 (-200.0~400.0)
OUT1,2:RELAY
SU-105ip
ic(-50.0~150)
OUT1,2:RELAY
Thank for purchasing Products of SAMWON ENG.
Instruction Manual is provided to prevent Products from being
damaged or defected by users mistake and to inform user the accurate
how to use. Please keep it in safe place. Thank you.
!
Warning
It’ s not guaranteed to prevent any hazards in personal, property, and
expensive peripheral, as it’ s not provided for the purpose of safety.
Please utilize additional duplex safety instruments.
Danger
①Electrical shock Please do not access to any AC terminal, while
in use. Electrical shock is expected.
②Please shut down the electrical power, whenever you check the
power input.
!
Caution
1.
A terminal (M3.5, Wide 7.2mm in maximum) shall be used to
connect AC power.
2.
A hazard in personal and property is expected, when you do not
follow the instructional recommendation by manufacturer.
3.
A keen attention shall be expected to ensure that any ingress of
dirt, water, oil and debris of cable do not exist inside the product, in
order to prevent any damage on product and a fire hazard
.
4.
Any modification and disassembly are not allowed. It may cause a
critical damage on product.
5.
Relay durability depends on the load capacity and the on-off
frequency. * durability : mechanical durability (a million times),
electrical durability (0.1 million times at AC250VAC 2A)
6.
Connect the terminal by confirming the polarity and usage.
7.
Isolate the wiring from the cable of high-voltage, electrical power
and motor in order to prevent any derived noise.
8.
Avoid the followings.
①dirt, corrosion gas, oil, humidity.
②danger of high humidity and freeze.
③radiant heat of sun shine.
④vibration impact.
⑤altitude higher than 2,000M.
⑥less than grade 2 environment.
9.
Power switch or a circuit breaker are recommended for shut-down.
10.
Utilize a switch or a circuit breaker equivalent to IEC947-1 or
IEC947-3 to be attached to panel.
11.
An authorized Compensating Lead Wires shall be used as a extension wire
which connects Thermo Couple and Controller. Normal Lead Wire may cause
a differential in temperature at the wiring connection between Thermo
Coupleand Normal Lead Wires.
A sensor cable longer than 3M may
cause a variation of temperature.
Correct it by using compensation
feature(rSt).
12.
When RTD sensor is selected, extension of wire shall be connected in 3
wires, which have the same thickness and length. A different resist in wire
may cause a differential in temperature.
A sensor cable longer than 3M
may cause a variation of temperature/humidity. Correct it by using
compensation feature(rSt).
13.
Isolate the product from the power cable to prevent any noise.
14.
Avoid the equipment which creates a strong high frequency noise,
such as welding machine, a sewing machine and SCR controller.
15.
Utilize additional terminal to be used in solenoid valve.
16.
Turn controller off when lighting and thunder.
17.
Mobile radio may cause a defect. Please refrain.
* Please pay keen attention to above. It may cause a defect to product.
on-off control or PI control for cooler/heater only.
Variation(dIF) 0.1~25.0, Delay timer of power-on switch for 0~300
seconds. Selectable in right/opposite direction.
Proportional, Integral compensation, Period timer (1~120seconds) to be
selectable.
Digital period timer inside for Defreeze. 999minutes in max.
(controllable by every minute/second.)
Lock feature for installer. / Allowance of range.
˚ Preset temperature could be regulated in range. Allowance of range
˚ Feature shall be locked. (Hysteria, Delayed time, direction..)LOCK
feature
In case of error in sensor, output leveling feature.(applied to TH, IC, HUM,
A only)
Supply power to controller to display current Temperature.
Set key only once. Set indicator blinks.
Use Up(Up),Down(Dn) key to reset Temperature.도를
Up/Down key for longer than 1 second will
speed up its feature.
If
Allowance of range
is on state,
reset range will be limited in the
dedicated range.
Set key once more again will
Memorize the reset value.
Even if power is turned-off, its set
Set value will not be erased.
Current temperature is displayed
And controller will be active.
Main output shall be connected
to terminal 6~7.
Terminal 5 is not available, only for OFF use.
For Aux output(Alarm/Timer), please refer to
<9. reset alarm output> and <10. set period timer>.
Display
Display the current & set temperature.
Main/AuxOutput
Display on-off state of main/aux output.
SET
Up
Down
Temperature to be set.
Up to amend preset.
Down to amend preset.
1. Picture
set
up
dn
< Terminal in
back>
Coil Terminal
코일단자
Magnet
메인
전원
작동
기계
AC
220V
Main
Pwr
Mac
hine
<current temp.>
Sensor
input
Main
output
Aux
output
Power
RELAY
5A
RELAY
2A
AC
220V
SET
up
dn
OUT1
OUT2
set
Up button
Main Output
Aux Output
Down button
Display
Question and Answer IconNeed help?

Do you have a question about the Samwon ENG SU-105 and is the answer not in the manual?

Overview

The SAMWON ENG SU-105 is an instrument designed for automatic temperature control, offering both On/Off and Proportional-Integral (PI) control methods. It supports various sensor types, including K-type and T-type thermocouples, Pt100 Resistance Temperature Detectors (RTDs), and IC sensors, making it versatile for a range of temperature monitoring and control applications.

Function Description:

The primary function of the SU-105 is to maintain a desired temperature by controlling external heating or cooling elements. It achieves this through two main control modes:

  • On/Off Control: This mode simply switches the output on or off based on whether the current temperature is above or below the setpoint, with an adjustable hysteresis (dIF) from 0.1 to 25.0°C. It also includes an ON Delay Timer (dLt) adjustable from 0 to 300 seconds, allowing for delayed activation of the output.
  • PI Control: This advanced mode uses proportional (P) and integral (I) compensation to achieve more precise temperature control, minimizing overshoot and steady-state errors. The proportional band is adjustable from 0.1 to 50.0, and the integral compensation helps eliminate offsets. A Period Timer (tYP) from 1 to 120 seconds determines the ON/OFF period for relay output.

The device features two outputs: a Main Output and an Auxiliary Output. The Main Output is dedicated to temperature control (heating or cooling), while the Auxiliary Output can be configured for either Alarm Output or Period Timer Output.

Alarm Output (Auxiliary Output): When configured as an alarm, it can activate based on a separate set temperature (SV2) and a differential range (dF2) from 0.1 to 25.0. It also includes a delay timer (dt2) from 0 to 300 seconds and can be set for heating (H) or cooling (C) direction. This allows for alerts or secondary control actions when the temperature deviates from a specific range.

Period Timer Output (Auxiliary Output): When configured as a period timer, it allows for scheduled ON/OFF cycles. Users can set the time unit (minutes or seconds), the initial output state (ON or OFF), and the ON (ton) and OFF (toF) durations, ranging from 0 to 999. A value of 0 for ton or toF signifies a continuous state. This is useful for applications requiring timed operations independent of temperature.

PRESET OUT Feature: This is a safety feature designed for TH, IC, HUM, and A sensors. In case of a sensor error during operation, it prevents immediate shutdown and instead levels the output value based on prior output data. This helps minimize damage and ensures a more graceful failure mode. It operates only in On/Off control mode, with On/Off times within 1 second/18 hours on average, and recalibrates every 30 outputs.

Important Technical Specifications:

  • Power Supply: AC100-220V (50/60Hz both) ±10%.
  • Power Consumption: Less than 5VA.
  • Input Sensors:
    • Thermocouple (K/T(CA)): Allowed wiring resistance less than 100Ω.
    • Resistance Temperature Detector (Pt100Ω): Allowed wiring resistance less than 50Ω.
  • Indication Level Accuracy:
    • Thermocouple: ±0.5% +1 digit of indicated value.
    • Resistance Temperature Detector: ±0.2%.
  • Variation (dIF): 0.1°C to 25.0°C.
  • Control Output:
    • Relay Contact Point: AC250V 5A (resistive load).
    • Durability: Higher than 300,000 operations (rating load).
  • Operating Environment:
    • Temperature: 0°C to 50°C.
    • Humidity: Less than 85% RH.
  • Sensor Compensation (rSt): Adjustable from -30 to +30.
  • Decimal Point: Selectable (0, 1, 2 for 100, 10.0, 1.00 respectively).
  • Display Range: -999 to +999 (for A sensor).

Usage Features:

  • Intuitive Interface: The device features an LCD display showing current and set temperatures, along with indicators for Main and Auxiliary output states. Up, Down, and Set buttons are used for navigation and parameter adjustment.
  • Easy Setup: Parameters are configured through a menu-driven system, accessed by pressing the SET key for 3 seconds. The menu structure is organized for logical progression through control modes, alarm settings, and period timer configurations.
  • Lock Feature: An "Installer's RESET" menu allows for locking certain features (Hysteria, Delayed time, direction) to prevent unauthorized changes, ensuring system stability. The "Allowance of range" feature can limit the preset temperature range.
  • Sensor Compensation: The SU-105 allows for sensor compensation (rSt) to correct for inaccuracies caused by long sensor wires or environmental factors, ensuring precise temperature readings.
  • Decimal Point Adjustment: The decimal point position can be adjusted for different levels of precision in temperature display.
  • Panel Mount Design: The device is designed for panel mounting, with a cutout size of 70+0.6 mm x 28+0.6 mm, and external dimensions of 76 mm (width) x 34 mm (height) x 70 mm (depth).

Maintenance Features:

  • Error Detection: The device displays "Err" in case of wiring errors or sensor malfunctions.
  • PRESET OUT for Sensor Errors: As described above, this feature helps mitigate the impact of sensor errors by leveling output values, preventing abrupt shutdowns and allowing for continued operation in a controlled manner.
  • Clear Wiring Diagram: The manual provides a clear wiring diagram for connecting sensors, power, and outputs, facilitating correct installation and troubleshooting.
  • Robust Design: Built to operate within a temperature range of 0°C to 50°C and humidity below 85% RH, ensuring reliability in various industrial environments.
  • Durability: The relay contacts are rated for over 300,000 operations, indicating a long operational life. Mechanical durability is rated at a million times, and electrical durability at 0.1 million times at AC250VAC 2A.

Safety Precautions:

The manual emphasizes several safety precautions:

  • Electrical Shock: Do not access AC terminals while in use. Always shut down electrical power before checking power input.
  • Environmental Protection: Prevent ingress of dirt, water, oil, and cable debris to avoid damage and fire hazards.
  • No Modifications: Do not modify or disassemble the product, as this can cause critical damage.
  • Wiring: Connect terminals by confirming polarity and usage. Isolate wiring from high-voltage cables, electrical power, and motors to prevent noise.
  • Avoid Harsh Conditions: Protect from dirt, corrosive gases, oil, humidity, freezing, direct sunlight, vibration, and altitudes higher than 2,000m.
  • Power Switch/Breaker: Use a power switch or circuit breaker (IEC947-1 or IEC947-3 equivalent) for shutdown.
  • Sensor Wiring: Use authorized compensating lead wires for thermocouples and RTDs. For RTDs, ensure three wires of the same thickness and length are used.
  • Noise Prevention: Isolate the product from power cables and avoid equipment that generates strong high-frequency noise (e.g., welding machines).
  • Mobile Radio: Refrain from using mobile radios near the device, as they may cause defects.
  • Lightning/Thunder: Turn off the controller during lightning and thunder.