EasyManua.ls Logo

Sanyo Big PACi 18 Series - Page 123

Sanyo Big PACi 18 Series
275 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1
1-118
This unit requires no additional refrigerant
charge up to tubing length 30 m. In case
of more than 30 m, additional refrigerant
charge is required. Refer to Tables 1-1 and
1-3.
In case of multi type installation, indoor
units should be installed within the
same room. If multi type indoor units are
installed in different rooms, temperature
control may develop problems because
thermostat operation must follow the
thermostat condition of 1 indoor unit only
(the main unit).
1.
2.
CAUTION
WARNING
Always check the gas density
for the room in which the unit is
installed.
Check of limit density
When installing an air conditioner in a room, it is
necessary to ensure that even if the refrigerant gas
accidentally escapes, its density does not exceed the
limit level.
If the density might exceed the limit level, it is
necessary to set up an opening between it and the
adjacent room, or to install mechanical ventilation
which is interlocked with a leak detector.
(Total refrigerant charged amount: kg)
(Min. indoor volume where the indoor unit is installed: m³)
<
Limit density 0.3 (kg/m
3
)
The limit density of refrigerant which is used in this
unit is 0.3 kg/m
3
(ISO 5149).
The shipped outdoor unit comes charged with the
amount of refrigerant fi xed for each type, so add it
to the amount that is charged at the fi eld. (For the
refrigerant charge amount at shipment, refer to the
unit’s nameplate.)
Minimum indoor volume & fl oor area relative to the
amount of refrigerant are roughly as given in the
following table.
10
13.5
27.0
40.5
54.0
67.5
81.0
94.5
108
121.5
135
5
10
15
20
25
30
35
40
45
50
m
3
m
2
Total amount of refrigerant
Min. indoor floor area
(when the ceiling is 2.7 m high)
Min. indoor volume
20 30 40 kg
Range below the
density limit of
0.3 kg/m
3
(Countermeasures
not needed)
Range above the
density limit of
0.3 kg/m
3
(Countermeasures
needed)
CAUTION
Pay special attention to any
location, such as a basement
or recessed area, etc. where
leaked refrigerant can
collect, since refrigerant gas
is heavier than air.
SM830161Book.indb118SM830161Book.indb118 2008/06/039:08:112008/06/039:08:11

Table of Contents

Related product manuals