1
1-134
1
Reference diagram for snow-proof duct - 2
Space requirements for setting - (2)
The models of SPW-C706 / 906VH8 with STK-BDV160E
Outdoor unit
SPW-C706 / 906VH8
OP
1000 150
Min. 250*
or more
Min. 250*
or more
Min. 300 or more
Min. 2000 or more
Q
Q
Min. P
or more
Min. O
or more
Min. 1000
or more
Min. 300
or more
(1) Single-unit installation
(2) Obstacles on both sides
Installation is possible with the maximum 3 outdooor units.
[Installation in front-rear rows]
[Obstacles to the front and rear of unit]
The top and both sides must remain open. Either the obstacle to the front or
the obstacle to the rear must be no taller than the height of the outdoor unit.
Dimension Q
If a snow protection duct is attached after the unit is
installed, verify that dimensionQ is 500 mm or more.
The top and both sides must remain open. Either the obstacle to the front or the obstacle
to the rear must be no taller than the height of the outdoor unit.
Note:
The amount of space required for removing the screw on the rear of the unit.
If in case the sufficient space for maintenance is ensured on the rear of the outdoor unit, installation
is possible with the space of both sides of not less than 150mm where marked with * mark.