1-56
1
1-2. Major Component Specifi cations
(A) Indoor Units
Ceiling-Mounted Type SPW-TDR184GH56 (A/B), T185H
MODEL No.
SPW-TDR184GH56 (A/B), T185H
Source
220 - 230 - 240V, single-phase, 50/60Hz
Controller P.C.B. Ass'y
CR-SXRP56B-B (Microprocessor)
Fan (Number...diameter, depth)
Centrifugal (2...ø140, L180)
Fan motor
Model...Nominal output W DK8-63C280H...30W
Source 280/340V (DC), 3-phase
No. of pole...rpm (230V, High) rpm 8P...960
Coil resistance
(Ambient temperature 20°C)
Ω
RED–WHT : 53.0
WHT–BLK : 53.0
BLK–RED : 53.0
Run capacitor VAC, µF –
Safety device
overcurrent, rotating signal detection, fuse
Electronic expansion valve
Coil –
Coil resistance (at 20°C)
Ω
–
Valve body –
Heat Exchanger
Coil Aluminium plate fin / Copper tube
Rows...fin pitch mm 3...1.4
Face area m
2
0.154
Panel
Model No. –
Dew proof heater –
Auto louver motor –
Coil resistance (at 20°C)
Ω
–
Drain Pump
Rated VAC, W –
Total head & capacity –
SM830161Book.indb56SM830161Book.indb56 2008/05/1920:33:132008/05/1920:33:13