4-7
4
12) Demand Control
Demand input from an external source is carried out from the outdoor unit EXCT (CN030) PCB or the
outdoor unit's serial/parallel I/O (optional).
(1) Demand via External Input
Demand control is carried out proportionally with the normal settings from the outdoor unit without any
external input.
(2) Demand Control with No External Input
* The operational current is restricted to either A% or B% as a general indicator during demand input.
There are two styles of demand operations available as methods of restraining power consumption.
13) Switching to Silent Mode Setup
Two silent mode settings are available: 50dB (A) and 45dB (A).
This setting can be amended with the detailed settings on the outdoor maintenance remote controller.
Demand control with EXCT input
Item code "21" : 0 (Setting at shipment) Sets silent mode 45dB (A).
Item code "21" : 1 Sets silent mode 50dB (A)
A% and B% can be amended in calibrations of 5% between 70% and 100% with the outdoor unit's
maintenance remote controller.
For details on how to amend the parameters, see the chapter on the outdoor maintenance remote
controller, (Refer to the section "6-6. Settings Modes : Setting the Outdoor Unit EEPROM").
Amendments can be made in calibrations of 5% between 70% and 100%.
Refer to the section "6-6. Settings Modes : Setting the Outdoor Unit EEPROM" for the outdoor
maintenance remote controller for details on how to amend the parameters.
Parameters are amended with item code "52" (current control level).
A% value amendments: Parameters are amended with item code "50" (demand 1).
B% value amendments: Parameters are amended with item code "51" (demand 2).
1
1
0
0
2P and 3P
Short-circuit
Control (range of operations)
1
0
1
0
Control OFF
Rated current restricted to B% (B% = 70% at factory shipment)
Rated current restricted to A% (A% = 100% at factory shipment)
No control
1P and 3P