Outdoor Unit : CMH1972A
Indoor Unit : XMHS1272 × 3
Power Supply : 230V Single Phase 60Hz
< Heating Capacity >
TH : Total Heating Capacity (BTU/h)
1.
Rating conditions (#)
: Indoor Unit Entering Air Temp. 70 °F (21.1 °C) D.B.
: Outdoor Ambient Temp. 47 °F (8.3 °C) D.B. / 43 °F (6.1 °C) W.B.
2.
3. Above data represents the value when the operation frequency of a compressor is fixed.
Above data does not take Defrost Operation, Overload Prevention Protection, and/or Cold Air
Prevention Protection during heating operation into account. For this reason, the value may vary
from the actual heating characteristics.
NOTE
MFC308:ETAR WOLF RIAh/UTB000,42 :YTICAPAC GNITAR
ROODNIROODTUO
ENT. TEMP.
o
F (
o
.PMET TNEIBMA)C
o
F (
o
C)
0857075606.B.W
(15.6) (18.3) (21.1) (23.9) (26.7)
0 (-17.8) TH 13,310 13,30013,270 13,24013,200
CI
1.10 1.15 1.21 1.27 1.32
3 (-16.1) TH 13,760 13,74013,720 13,69013,650
CI
1.11 1.17 1.23 1.28 1.34
8 (-13.3) TH 14,830 14,82014,790 14,76014,720
CI
1.14 1.20 1.26 1.33 1.39
13 (-10.6) TH 15,950 15,930 15,910 15,87015,830
CI
1.17 1.24 1.31 1.38 1.44
18 (-7.8) TH 17,18017,160 17,130 17,09017,040
CI
1.20 1.28 1.35 1.43 1.50
23 (-5.0) TH 18,47018,450 18,420 18,38018,320
CI
1.24 1.32 1.40 1.48 1.56
28 (-2.2) TH 19,82019,800 19,770 19,72019,660
CI
1.27 1.36 1.45 1.54 1.62
33 (0.6) TH 21,22021,190 21,160 21,10021,040
CI
1.31 1.40 1.50 1.59 1.68
38 (3.3) TH 22,61022,580 22,540 22,48022,410
CI
1.34 1.44 1.54 1.65 1.74
43 (6.1) TH 24,08024,050 # 24,00023,94023,860
CI
1.38 1.49 1.60 1.70 1.81
48 (8.9) TH 25,58025,540 25,490 25,42025,340
CI
1.42 1.53 1.65 1.76 1.87
53 (11.7) TH 27,09027,050 27,00026,92026,830
CI
1.58 1.70 1.70 1.82 1.94
58 (14.4) TH 28,560 28,520 28,460 28,38028,280
CI
1.50 1.62 1.75 1.88 2.01
63 (17.2) TH 30,090 30,040 29,970 29,88029,780
CI
1.55 1.68 1.81 1.95 2.08
65 (18.3) TH 30,680 30,630 30,560 30,47030,360
CI
1.56 1.70 1.84 1.98 2.11