5-3. Cooling Capacity
Indoor Unit SAPK161GJA
Outdoor Unit SAPC161GA
240V Single Phase 50Hz
RATING CAPACITY 4.70 kW
AIR FLOW RATE 760
m
3
/h
EVAPORATOR CONDENSER
ENT. TEMP. °C OUTDOOR AMBIENT TEMP. °C
W.B. D.B. 30 35 40 43
TC 4.32 4.12 3.87 3.56
CM 1.25 1.34 1.45 1.60
21 SHC 2.92 2.81 2.68 2.53
15 23 SHC 3.27 3.16 3.04 2.89
25 SHC 3.63 3.52 3.39 3.24
27 SHC 3.98 3.87 3.75 3.56
29 SHC 4.32 4.12 3.87 3.56
31 SHC 4.32 4.12 3.87 3.56
TC 4.64 4.42 4.15 3.82
CM 1.28 1.38 1.49 1.64
21 SHC 2.55 2.45 2.32 2.17
17 23 SHC 2.91 2.80 2.67 2.52
25 SHC 3.26 3.16 3.03 2.88
27 SHC 3.62 3.51 3.38 3.23
29 SHC 3.97 3.87 3.74 3.59
31 SHC 4.33 4.22 4.09 3.82
TC 4.94 # 4.70 4.42 4.07
CM 1.32 1.42 1.54 1.69
21 SHC 2.17 2.06 1.94 1.79
19 23 SHC 2.52 2.42 2.29 2.14
25 SHC 2.88 2.77 2.65 2.50
27 SHC 3.23 3.13 3.00 2.85
29 SHC 3.59 3.48 3.36 3.21
31 SHC 3.94 3.84 3.71 3.56
TC 5.23 4.98 4.68 4.31
CM 1.36 1.46 1.58 1.73
23 SHC 2.13 2.03 1.91 1.76
21 25 SHC 2.49 2.38 2.26 2.11
27 SHC 2.84 2.74 2.62 2.47
29 SHC 3.20 3.09 2.97 2.82
31 SHC 3.55 3.45 3.33 3.18
TC 5.54 5.23 4.90 4.55
CM 1.39 1.50 1.62 1.78
23 25 SHC 2.07 1.95 1.83 1.70
27 SHC 2.43 2.31 2.18 2.06
29 SHC 2.78 2.66 2.54 2.41
31 SHC 3.14 3.02 2.89 2.77
TC : Total Cooling Capacity (kW)
SHC : Sensible Heat Capacity (kW)
CM : Compressor Input (kW)
Rating conditions (#Mark) are
Outdoor Ambient Temp. 35°C D.B.
Indoor Unit Entering Air Temp. 27°C D.B. / 19°C W.B.