Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at
Rating Conditions Running Amps. A 0.42 0.60 13.48 14.5
Power Input kW 0.086 0.131 2.673 2.89
SSA 385, 386 Running Amps. 0.42 0.60 15.78 16.8
Conditions Power Input 0.086 0.131 3.173 3.39
Full Load Conditions Running Amps. A 0.42 0.60 18.98 20.0
Power Input kW 0.086 0.131 3.863 4.08
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
SSA 385, 386 Conditions (Saudi standard)
: Indoor Air Temperature 29°C D.B. / 19°C W.B.
Outdoor Air Temperature 46°C D.B. / 24°C W.B.
Full Load Conditions : Indoor Air Temperature 29°C D.B. / 19°C W.B.
Outdoor Air Temperature 54°C D.B.
Indoor Unit SAP–K241GJA SAP–K241MBA
Outdoor Unit SAP–C241JA SAP–C241BA
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at
Rating Conditions Running Amps. A 0.39 / 0.40 0.49 / 0.50 11.92 / 11.90 12.8 / 12.8
Power Input kW 0.075 / 0.080 0.106 / 0.118 2.469 / 2.562 2.65 / 2.76
Full Load Conditions Running Amps. A 0.39 / 0.40 0.49 / 0.50 16.62 / 15.90 17.5 / 16.8
Power Input kW 0.075 / 0.080 0.106 / 0.118 3.509 / 3.542 3.69 / 3.74
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 52°C D.B.
Indoor Unit SAP–K241GJA SAP–K241MBA
Outdoor Unit SAP–C241GA SAP–C241MA