16
5-3. Cooling Capacity
240V Single Phase 50Hz
Indoor Unit SAPK181GJH
Outdoor Unit SAPC181GH
RATING CAPACITY 5.05 kW
AIR FLOW RATE 760
m
3
/h
EVAPORATOR CONDENSER
ENT. TEMP. °C OUTDOOR AMBIENT TEMP. °C
W.B. D.B. 30 35 40 43
TC 4.65 4.42 4.16 3.83
CM 1.81 1.94 2.13 2.37
21 SHC 3.09 2.97 2.83 2.66
15 23 SHC 3.44 3.32 3.18 3.02
25 SHC 3.80 3.68 3.54 3.37
27 SHC 4.15 4.03 3.89 3.73
29 SHC 4.51 4.39 4.16 3.83
31 SHC 4.65 4.42 4.16 3.83
TC 4.98 4.75 4.46 4.11
CM 1.86 2.00 2.18 2.43
21 SHC 2.72 2.61 2.47 2.30
17 23 SHC 3.08 2.96 2.82 2.65
25 SHC 3.43 3.32 3.18 3.01
27 SHC 3.79 3.67 3.53 3.36
29 SHC 4.14 4.03 3.89 3.72
31 SHC 4.50 4.38 4.24 4.07
TC 5.30 # 5.05 4.75 4.37
CM 1.92 2.06 2.25 2.50
21 SHC 2.34 2.22 2.08 1.92
19 23 SHC 2.69 2.58 2.44 2.27
25 SHC 3.05 2.93 2.79 2.63
27 SHC 3.40 3.29 3.15 2.98
29 SHC 3.76 3.64 3.50 3.34
31 SHC 4.11 4.00 3.86 3.69
TC 5.62 5.35 5.03 4.63
CM 1.97 2.12 2.31 2.57
23 SHC 2.30 2.19 2.05 1.88
21 25 SHC 2.66 2.54 2.40 2.24
27 SHC 3.01 2.90 2.76 2.59
29 SHC 3.37 3.25 3.11 2.95
31 SHC 3.72 3.60 3.47 3.30
TC 5.95 5.62 5.26 4.89
CM 2.02 2.17 2.37 2.63
23 25 SHC 2.24 2.10 1.97 1.83
27 SHC 2.59 2.46 2.32 2.18
29 SHC 2.95 2.81 2.67 2.54
31 SHC 3.30 3.17 3.03 2.89
TC : Total Cooling Capacity (kW)
SHC : Sensible Heat Capacity (kW)
CM : Compressor Input (kW)
Rating conditions (#Mark) are
Outdoor Ambient Temp. 35°C D.B.
Indoor Unit Entering Air Temp. 27°C D.B. / 19°C W.B.